Visual Comfort Study

The Daylight Availability Study yielded a building massing and façade layout that provides daylight in all key areas of a building over the course of the year. The goal of this design exercise is to check for potential areas of discomfort glare (Task A) and (if necessary) to develop a shading strategy to control for it.

Task A: Discomfort Glare

Starting off with your final design from the Daylight Availability Study, lay out furniture, interior walls and seating arrangements to identify regularly occupied areas (which should be glare free) versus circulation areas. Select a representative, reguarly occupied study area that is exposed to a fair amount of direct sunlight (see ASE analysis). In case you are working on the Multi-Unit Residential project, focus your glare analysis on a dedicated area within a south-facing apartment that will function as a home office. Generate an annual Daylight Glare Probability (DGP) map of your study area to identify when and where glare occurs in your building (Figure 1 and 2).

Identify the cause of glare for a few problematic situations by selecting a representative location (avatar) and consulting the avatar’s hourly glare map (Figure 3). What are the times of day and dates ranges in the year with frequent periods of discomfort glare? For example, for the avatar in Figure 1 facing east, glare mainly occurs February/March and October during mid-day.

Figure 3 Annual glare map for the avatar in Figure 1

As shown in this video tutorial, create a hemispheric glare map of a typical situation (say Feb 18 at 9:30am) and fine-tune your façade design to avoid visual discomfort. Possible changes include adjusting your window layout and glazing type, adding a static shading system and/or specifying a roller shade. Show a visualization before and after the intervention (Figure 4).

Figure 1 Daylight Glare Probability distribution of an example open plan office

Figure 2 Daylight Glare Probability distribution in a home office

Figure 4 Glare analysis of the avatar from Figure 1 on Feb 18 at 11:30am with and without a static external shading system

Provide an annual daylight glare probability analysis of a revised design once you are satisfied with your improvements. Note that apart form geometric façade modifications, you may also simply specify a dynamic shading system.

Figure 5 Daylight Glare Probability distribution of the revised design for an office floor plan

Remember to rerun a daylight availability simulation for the revised design.